Fire Door Ratings in India: What FD30 to FD120 Mean and How to Check Your Doors

A fire door holds back fire and smoke for a rated time, but only when it is shut. This guide explains what ratings such as FD30 to FD120 mean, why the old IS 3614 Part 1 and Part 2 have been replaced by IS 3614:2021, why the rating covers the whole door set, and how to check that the fire doors in your building close and latch on their own.

TopicFire SafetyUpdated2026-09-16
01
The guide
Editorial cover for Fire Door Ratings in India: What FD30 to FD120 Mean and How to Check Your Doors

Quick answers

What do fire door ratings like FD30 and FD60 mean?

The rating shows how long the door set held back fire in a standard test. FD30 means 30 minutes, FD60 means 60 minutes, FD90 means 90 minutes and FD120 means 120 minutes.

Which Indian standard applies to fire doors?

The current BIS standard is IS 3614:2021, Specification of Fire Doors and Assembly. It replaced IS 3614 Part 1 and Part 2, which have been withdrawn.

Which fire door rating is used in factories and warehouses?

Sites with flammable materials or hazardous processes usually need higher ratings such as FD90 or FD120, to allow more time for escape and for the fire brigade to arrive. The exact rating is set by the fire plan and local rules.

When should a fire door be replaced?

When it is damaged beyond repair, will not close and latch properly, or fails an inspection. A renovation, a change of use or new fire rules can also mean new or upgraded doors.

Walk down the staircase of most office buildings or high-rise societies and you will pass a heavy door with a closer at the top. Often it is propped open with a brick or a fire extinguisher. That is a fire door, and propped open it does nothing.

A fire door holds back fire and smoke for a set time, so people can get down the stairs and the fire brigade can work. Here is what the ratings mean, which Indian standard applies now and how to tell whether the doors in your building will do their job.

Infographic: fire door ratings FD30, FD60, FD90 and FD120 drawn as 30 to 120 minutes of fire resistance, with a six-point door check: it closes and latches by itself, nothing props it open, seals and gaps are right and there is no damage.

What the ratings mean

Fire doors are rated by how long they held back fire in a standard test. You will often see these labels:

  • FD30: 30 minutes of fire resistance
  • FD60: 60 minutes
  • FD90: 90 minutes
  • FD120: 120 minutes

The “FD” labels are widely used in the trade. Indian drawings and test certificates often give the rating simply in minutes or hours, so go by the rating on the certificate, not a sticker. Which rating a door needs depends on the building and where the door is, and is set by the National Building Code of India 2016, your local fire rules and the approved fire plan.

Indian standards for fire doors

An earlier version of this page listed IS 3614 Part 1 and Part 2. Both have since been withdrawn. BIS replaced them with IS 3614:2021, “Specification of Fire Doors and Assembly”, a revision of the two older parts. If a supplier still quotes the old parts, ask why.

A rating belongs to the whole door set: the leaf, frame, hinges, glazing, seals, closer and other hardware that were tested together. Change one part, and the rating may no longer hold.

Where fire doors are used

In offices, schools, hotels, hospitals and residential towers, fire doors split the building into compartments and protect staircases and lobbies. A fire on one floor then stays on that floor for longer, and the stairs stay clear of smoke while people get out.

Factories and warehouses with flammable materials or hazardous processes usually need higher ratings, such as FD90 or FD120, to give more time for escape and for the fire brigade to arrive. The exact rating is a design decision for your fire consultant and the fire authority.

Keeping fire doors working

A fire door is only as good as its last check. Hinges sag, closers fail, seals get painted over and someone drills a hole for a cable. Look at each door regularly:

  • It swings shut and latches on its own from any open position.
  • Nothing is holding it open: no wedge, hook, brick or chair.
  • The seals round the frame are in place and not painted over.
  • The gaps between door and frame are no wider than the maker allows.
  • There are no holes, ordinary glass panels or damage on the door.
  • Doors that must stay shut carry a “Fire door, keep shut” sign.

When to replace a fire door

Replace a fire door if it is damaged beyond repair, will not close properly or fails an inspection. A renovation, a change in how the space is used or new fire rules can also mean new or upgraded doors. Never swap a fire door for an ordinary door during interior work.

Check one door today

Open the fire door on your floor or staircase and let go. It should swing shut and latch by itself. If it does not, or if you find it wedged open, write to your building manager or society secretary today.

What needs attention

  • A fire door holds back fire and smoke for its rated time only if it is closed
  • Ratings describe how long a door set resisted fire in a test; higher-risk areas need longer ratings
  • IS 3614 Part 1 and Part 2, quoted in the earlier article, have been withdrawn and replaced by IS 3614:2021
  • A door wedged open, with a broken closer or gaps round the frame, gives little protection
  • Door frame, hinges, glazing, seals and closer must all be part of the tested set

Controls that reduce risk

  1. Buy fire doors with test certificates for the rating you need, and ask which standard they were made to
  2. Have them installed with the matching frame, hinges, seals and closer
  3. Check every month that each fire door closes and latches on its own
  4. Repair closers, seals and damaged doors quickly
  5. Put "Fire door, keep shut" signs on doors that must stay closed
  6. Review fire doors after any renovation or change of use

Common unsafe practices

  • Wedging fire doors open for convenience
  • Removing or disconnecting the door closer
  • Cutting holes for cables or fitting ordinary glass panels
  • Replacing a fire door with an ordinary door during renovation
  • Buying a door without test certificates for the full set
  • Ignoring gaps, damaged seals or a door that does not latch
02
Watch & learn

Related Videos

Relevant safety learning

Fire Doors and Doorsets Specification — IS 3614:2021 Explained — Fire Safety Standards in India

Fire Safe India by MK · English

Detailed explanation of IS 3614:2021 fire doors and doorsets specification.

03
Facts & action

Evidence, Cases & Next Steps

What the evidence supports

  • What a rating means | How long the door set held back fire in a standard test
  • Common labels | FD30, FD60, FD90 and FD120, meaning 30 to 120 minutes
  • Current Indian standard | IS 3614:2021, Specification of Fire Doors and Assembly
  • Older standards | IS 3614 Part 1 and Part 2 have been withdrawn
  • What the rating covers | The whole set: door, frame, hinges, glazing, seals and closer
  • Who sets the rating needed | NBC 2016, local fire rules and the approved fire plan
  • Quick check | The door closes and latches by itself, with no wedge, gaps or damaged seals

Immediate prevention actions

  1. Find the fire doors on your floor or in your staircase
  2. Open one and let go; it should close and latch by itself
  3. Remove any wedge or hook holding a fire door open
  4. Look for gaps or damaged seals round the frame
  5. Report a faulty fire door to the building manager

Emergency survival steps

  1. Close fire doors behind you as you leave
  2. Feel a closed door before you open it, and use another route if it is hot
  3. Use the protected staircase, not the lift
  4. If you are trapped, keep the door shut and block gaps with wet cloth
  5. Call 101 or 112 and say which floor and room you are in

Limitations

  • Required ratings depend on the building type, the location of the door and local fire rules
  • The FD30 to FD120 labels in the article are widely used names; check the rating stated on your test certificate
  • The article gives no Indian figures on fire door failures
  • The full text of IS 3614:2021 was not reviewed for this page; ask your supplier or consultant for its test and marking requirements
  • Only a competent inspector can confirm that a door set meets its rating
Sources and further reading
Community discussion

Questions, experience and constructive safety discussion

Comments publish immediately unless security controls identify spam. Please do not post private information, unsupported allegations or unsafe instructions.

Leave a comment

* Name and email are required. Your email address will not be published.


The reCAPTCHA verification period has expired. Please reload the page.