Quick answers
What does NBC 2026 say about fire safety in schools?
It counts classrooms at 3.0 m2 of net area per person, asks for two doorways in rooms over 45 people, sets a minimum stair width of 1.50 m and limits dead ends to 6 m. The standard is voluntary until your state adopts it.
What is the maximum travel distance in a school or hospital?
Table 4 prints 30 m for construction Types 1 and 2 without sprinklers, 45 m with sprinklers and 22.5 m for Types 3 and 4, for both educational and institutional buildings.
How are people counted in a hospital under NBC 2026?
Table 2 uses 11.0 m2 of net area per person in wards, 7.0 m2 in outpatient areas and 12.0 m2 of gross area in nursing homes. The number actually declared is used if it is higher.
How big can a hospital fire compartment be?
Table 6 limits hospitals and nursing homes with beds to 750 m2 without sprinklers and 2,000 m2 with sprinklers. For buildings for the custody and care of children, convalescents and the aged, the figures are 750 m2 and 1,500 m2.
Do hospitals need sprinklers under NBC 2026?
In Table 7C the hospital rows from 501 m2 up to 45 m are CL-3 or higher and list sprinklers as required. Basements and rooms for oxygen or medical gas, laundry and transformers should be sprinklered to CL-3.
Is NBC 2026 mandatory for schools and hospitals?
No. It is voluntary until a state or local authority adopts it. Your state's building rules and the fire department decide what applies to your building.
NBC 2026 treats a school or college as an educational building and a hospital or nursing home as an institutional one. In a classroom the standard counts one person for every 3.0 m2 of net floor area. A dead-end corridor may not run past 6 m. The walk to a fire exit is capped at 30 m, or 45 m with sprinklers, for the two stronger construction types. For hospitals the firefighting table starts at 501 m2 and gets stricter with size and height. This is the twelfth chapter in our series on the 2026 national building standards. Checked 15 November 2026.
In short
- Schools and colleges: the standard’s scope starts above 9 m in height or 500 m2 on any floor. Self-certification by a State-approved professional is treated as acceptable up to 500 m2 and 24 m.
- Hospitals and nursing homes: scope starts above 15 m or 500 m2 on any floor. A hospital row of the firefighting table asks for sprinklers from 501 m2.
- Numbers to remember: 3.0 m2 per person in classrooms, 11.0 in wards, 7.0 in outpatient areas, 12.0 (gross) in nursing homes; 6 m dead-end limit; 1.50 m minimum stair width in schools and 2.00 m in institutions.
- It is voluntary for now. NBC 2026 binds a building only once your state adopts it. Your state rules and your fire officer decide for your building. We make no claim here about any Fire NOC rule.

Who this is for
School heads, college administrators, trustees, parents on a school committee, coaching class owners, and the people who run clinics, hospitals and nursing homes. If you only read one section, read the worked examples below. They show how the numbers work on a real floor.
Does the standard reach your building?
Part F of NBC 2026 says it applies to educational buildings taller than 9 m or with any floor larger than 500 m2. For institutional buildings, which include hospitals and nursing homes, the figures are 15 m and 500 m2. The standard adds that a State or local authority may change these values after looking at local fire risk. It also says a smaller building with a single staircase should have a firefighting-shaft type stair on the outer wall. Because states can change the numbers, treat these as the national starting point. Our overview of fire safety laws in India, NBC and state acts explains who decides what.
Schools and colleges: what the standard asks
Counting people
Table 2 gives a minimum occupant load. For educational buildings it is 3.0 m2 per person of net area. The standard says to use the number of people actually declared if that is higher. A 90 m2 classroom is therefore counted as at least 30 people. The standard also notes that net area is not the same as carpet area, so ask your architect how the floor was measured.
Doors, stairs and corridors
- Doorways: every room that can hold more than 45 people should have at least two doorways, and exit doors should have panic bars. A classroom door that opens straight outside may carry the same lock as the one to the corridor, but there must be no way of locking it against people leaving.
- Stair width: the minimum is 1.50 m for educational buildings.
- Dead ends: a dead-end corridor in the exit access should not exceed 6 m for educational, institutional and assembly buildings. For most other buildings the limit is 15 m.
- Travel distance: for educational buildings Table 4 prints 30 m for construction Types 1 and 2 without sprinklers, 45 m with sprinklers, and 22.5 m for Types 3 and 4. The architect knows the construction type from the approved drawings.
- Young children: preschool, kindergarten and Class 1 should be on the ground floor or the exit-discharge level. Class 2 should be no higher than one floor above it.
- Stores and labs: the building should not store hazardous material. Volatile flammable liquids are kept out too, and handling is limited to science laboratories.
- Very small schools: a building that holds not more than 20 pupils at any time may be used as a school, with two exceptions. Exterior walls, or parts of walls, less than 900 mm from the neighbouring plot line should have no openings. A classroom may have only one exit, not less than 900 mm wide. The clause says the building “will have only the first floor”. We read that as a single-storey building, which is our reading and not the standard’s words.
What the firefighting table asks, row by row
Table 7B ties installations to height and area. We describe the rows in words and have not copied the table. Please read the table itself, with its notes, for your building.
- Up to 500 m2 and up to 24 m: self-certification by a certified, State-approved building professional should be treated as acceptable.
- 24 m to 45 m, or under 24 m with 501 to 1,000 m2: protection level HL-3. Fire extinguishers, first-aid hose reels, a wet riser, yard hydrants, fire detection and alarm, and a public address and voice evacuation system are required. Sprinklers and a down comer are not required on this row.
- 1,001 m2 and above: protection level CL-4. The same list plus automatic wet sprinklers.
- 45 m to 60 m: also CL-4, with the same list as the row above.
- Above 60 m: the table sends you to a note, which asks for hydraulic calculations and says pumps should not exceed 12 bar shut-off pressure.
The notes add three things worth knowing. Laboratories, audio-visual or computer rooms and auditoriums in a school should be sprinklered to CL-3. A basement should also be sprinklered to CL-3. If there is an electric-vehicle park in a podium or basement, the protection level should comply with CL-5. HL and CL are the standard’s own labels for its protection levels, and we list what each row asks for rather than decode them.

Hospitals and nursing homes: what the standard asks
Counting people
Table 2 sets different factors by area. An inpatient area such as a ward is counted at 11.0 m2 per person of net area. An outpatient area is 7.0 m2 net. Nursing homes and daycare clinics are counted at 12.0 m2 per person of gross area. Note that the 12.0 is a gross figure and the 11.0 and 7.0 are net figures, so they should not be set side by side as like for like.
The firefighting table for hospitals
Table 7C has two sections that are both lettered “b)”, one for hospitals and one for custodial, penal and mental institutions. The rows run across several pages, which makes them easy to mix up. We checked each row against the page image. For hospitals, the rows read as follows.
- Up to 45 m, floor area 501 to 1,000 m2: protection level CL-3. Extinguishers, hose reels, a wet riser, yard hydrants, sprinklers, and detection and alarm are required. The public address and voice evacuation system is not required on this row.
- Up to 45 m, 1,001 m2 and above: CL-4. The same list, now with the public address system required too.
- Above 45 m up to 60 m: CL-5, with the same installations as CL-4.
- Above 60 m: the table points to a note on hydraulic calculations, multi-level pumping and a 12 bar limit on pump shut-off pressure.
Nursing homes and sanatoria have their own row. Above 15 m, or up to 15 m with 501 m2 and above, the level is HL-3. It asks for extinguishers, hose reels, a down comer and fire detection and alarm. It does not ask for a wet riser, yard hydrants, sprinklers or a public address system. Up to 500 m2 and 24 m, self-certification by a State-approved professional is treated as acceptable, as for schools.
The notes under Table 7C give one rule that matters for hospitals in particular. A basement, or any storage of oxygen or other medical gas, laundry or linen and waste, and transformer or HT rooms, should be protected with sprinklers to CL-3. Critical rooms such as these may also need the extra protection set out in the standard’s Tables 9, 10 and 11.
The custodial rows, as printed
The second “b)” section covers custodial, penal and mental institutions. The rows are unusual and we give them only as printed. From 501 to 1,000 m2 (HL-2) the row asks for extinguishers, hose reels, a down comer and a public address system, but shows detection and alarm as not required. From 1,001 m2 (HL-3), and above 45 m (HL-4), it asks for extinguishers, hose reels, a wet riser, yard hydrants, detection and alarm and a public address system. Sprinklers are marked not required on all three rows. We cannot explain the pattern, and we would rely on it only after asking the fire officer.
One more rule matters for these buildings. Clause 6.3.3 accepts that mental institutions and penal institutions may need locked doors and barred windows, and that some psychiatric patients cannot seek safety without guidance. To that extent it waives the usual rule that exits must stay unlocked. In return it asks for a reliable way to release people quickly, such as remote control of the locks or one set of keys that attendants commonly carry for all of them. Clause 6.3.2(e) says the same in other words: reliable means to permit prompt release of inmates from any locked section in a fire or other emergency. In our view, a lock is only as good as the person who can open it at 2 am, so ask who holds the keys at night.
Compartments, stairs and doors
- Compartment size (Table 6): hospitals and nursing homes with beds or sleeping patients are limited to 750 m2 per fire compartment without sprinklers and 2,000 m2 with them. For buildings used for the custody and care of children, convalescents and aged people who cannot protect themselves, the figures are 750 m2 and 1,500 m2.
- Stairs: the minimum stair width is 2.00 m for institutional buildings. The same clause also prints a maximum width of 2.00 m for stairs in hospitals, which we show as printed.
- Travel distance: Table 4 gives institutional buildings 30 m unsprinklered, 45 m sprinklered and 22.5 m for Types 3 and 4. Table 4 Note 1 limits the common path of travel to 50 per cent of these figures, while the hospital clause says the common path of travel should be up to 30 m. The two read differently. Ask the fire officer which governs.
- Dead ends: not more than 6 m in a hospital corridor.
- Move sideways first: for patients who cannot save themselves, the clause favours progressive horizontal evacuation. People are moved from the affected area through a fire-resistant wall into the next compartment (our deeper guide on why hospitals move patients sideways first explains how). Each compartment should be able to hold its own patients and those of the next one at 3.5 m2 per person, or 0.6 m2 if they are not bed-ridden.
- Doors and corridors: doors in the fire walls are self-closing, with electromagnetic hold-open, and the openings should be at least 2.0 m wide in double-swing double-leaf form. Corridors and ramps used to move patients should be at least 2.4 m wide. A patient room door should be at least 1.25 m for one or two beds.
- Critical rooms: operation theatres, delivery rooms, intensive care and recovery rooms for patients who cannot save themselves should be separated by at least 120 minutes of fire resistance.
Worked examples
These are illustrations only, with made-up numbers, and not checks of any real building. A real building has to meet every rule in the standard and in your state’s rules.
A coaching class on the second floor. Take a three-storey building, 11 m high, with 450 m2 on each floor. The building crosses the 9 m height line in clause 1.2, so we treat it as inside the standard. It is under 500 m2 and under 24 m, so a State-approved professional’s self-certification is treated as acceptable by the table. Whether a coaching class counts as an educational building is for your fire officer to say. Now check the floor. One hall is 150 m2, so at 3.0 m2 per person it is counted as 50 people. That is over 45, so it needs two doorways. The farthest desk is 8 m from the hall door and the corridor then runs 24 m to the stair door. The walk is 8 + 24 = 32 m. Without sprinklers that is 2 m over the 30 m limit. A second stair nearer that end solves it. A corridor that continues 10 m past the last exit door is a dead end 4 m over the 6 m limit, whatever the total walk. The self-certification line does not remove these checks. It tells you who may sign.
A 40-bed nursing home. Take a two-storey home of 10 m, with an 800 m2 floor holding 20 beds, plus staff and visitors. Counted at 12.0 m2 gross per person, 800 m2 gives about 67 people. That is a minimum, and the number actually declared is used if it is higher. The floor is over 501 m2, so the nursing home row in Table 7C applies: extinguishers, hose reels, a down comer and detection and alarm. It is also over the 750 m2 compartment limit for unsprinklered hospital-type buildings in Table 6, so the floor needs a fire barrier to make two compartments of about 400 m2. That fits the idea of moving patients sideways. Two compartments of 400 m2 are large enough, on paper, for 20 beds and 20 more from the next compartment at 3.5 m2 each, which is 140 m2. Whether the hospital clause for horizontal evacuation is applied to a nursing home is a point to confirm with the fire officer. If the home stores oxygen cylinders, that room needs sprinklers to CL-3 under the Table 7C notes.
What this means for different readers
- School heads: count classroom seats against 3.0 m2 per person, check which rooms hold more than 45, and walk the corridor from the farthest classroom to the stair. Our guide to the school fire safety plan covers the plan itself, and how to run a fire drill covers the practice.
- Parents: ask where the young classes sit. Preschool to Class 1 should be on the ground floor or the exit-discharge level, and Class 2 no more than one floor up.
- Hospital and nursing home managers: mark compartments on a plan, keep corridors at the required width, and know where oxygen, laundry and transformer rooms are. See what patients’ families and staff can do and the causes of hospital fires in India.
- Families of patients: ask a ward nurse where the nearest fire exit is and which way staff would move beds first.
Ask your fire officer
You can put these questions to the local fire officer, the architect or the management. They are fair questions for a school committee or a hospital board.
- Which version of the standard or which state rule applies to this building?
- What is the longest walk to a fire exit on each floor, and which construction type was it designed for?
- Is there any dead end longer than 6 m?
- Which row of the firefighting table does this building fall under, and are those installations working?
- For a hospital or home: how are the compartments divided, and where is the plan for moving patients sideways?
Where this stands in law
The National Building Construction Standards 2026, Part F, is voluntary. It binds a building only once a state or local authority adopts it, and until then your state’s building rules and the fire department decide what applies. We do not say here whether any school or hospital needs a Fire NOC. State rules decide that. Older buildings may have been approved under earlier rules. This guide is general safety information. It is not legal or engineering advice, and it does not tell you whether a particular building complies.
What we could not confirm
- How a state that has adopted the standard may have changed these numbers. We read the national standard only.
- Why the custodial rows of Table 7C are the way they are. We give them as printed.
- Which of two figures governs the common path of travel in an institutional building.
- Whether a coaching class or a nursing home is treated like a school or a hospital in a given state.
- The meaning of the protection levels HL and CL beyond what each row lists.
- The listed videos. They were checked for public status and embedding but not watched in full.
Do this today
Pick one floor of your school, college, clinic or home. Walk from the farthest room to the stair door and count the metres. Look for any corridor that ends in a wall. Check that no stair or exit has goods stacked in it. For hospitals, read our note on how to make an evacuation plan that works. Our guides on the deadliest hospital fires and on the standards in schools and colleges are in the related cards below. For more, read our chapters on exits and stairs and on fire compartments.
What needs attention
- Educational buildings are counted at 3.0 m2 per person net; rooms over 45 people need two doorways.
- Educational firefighting rows go from HL-3 without sprinklers to CL-4 with sprinklers at 1,001 m2 and above.
- Hospital rows start at CL-3 from 501 m2, with sprinklers, and reach CL-5 above 45 m.
- A basement, medical gas or oxygen storage, laundry and transformer rooms in institutional buildings should be sprinklered to CL-3.
- Hospitals and nursing homes are limited to 750 m2 per compartment unsprinklered, 2,000 m2 sprinklered.
- Custodial rows of Table 7C are unusual and should be read as printed.
- The standard is voluntary until a state adopts it.
Controls that reduce risk
- Check the building's height and floor area against clause 1.2.
- Count occupants for each hall and ward using Table 2.
- Walk the longest route to a stair and check for dead ends.
- Ask which row of Table 7B or 7C applies and whether the systems work.
- For a hospital or home, draw the fire compartments on a plan.
- Ask your fire officer about your state's rules.
Common unsafe practices
- Counting classroom occupants from carpet area instead of the standard's factor.
- Putting a hall of more than 45 people behind a single doorway.
- Measuring travel distance in a straight line instead of along the route.
- Letting a corridor run past the last exit as a dead end longer than 6 m.
- Reading the wrong "b)" section of the hospital table.
- Storing oxygen, linen or electrical gear in a basement without sprinklers.
- Treating this guide as proof that a building complies.